Nata Scope of Accreditation
SCOPE OF ACCREDITATION -No. 16641
ACCREDITATION NO: 16641
Switchmode Power Supplies Pty Ltd
Switchmode Power Supplies
1/37 Leighton Place
HORNSBY NSW 2077
Contact: Martin Griffith
PHONE: (02) 9476 0300 FAX: (02) 9476 0479 MOBILE:
EMAIL: martin.griffith@switchmode.com.au
WEB SITE: www.switchmode.com.au
Contact: Mr Graham Gillard
Mobile: 0403 657 702
Phone: (02) 9476 0300
Fax: (02) 9476 0479
Email: graham.gillard@switchmode.com.au
FACILITIES: Public testing service
This laboratory complies with the requirements of ISO/IEC 17025 (2005)
The uncertainty of measurement is reported as an expanded uncertainty having a level of confidence of 95% unless stated otherwise
1.39 Indicating and recording instruments 1.39 Indicating and recording instruments
.01 D.C. voltmeters
By the methods of - WI.WC.31
with least uncertainties of measurement of -
0.57% from 1 mV to 10 mV
0.058% from 10 mV to 120 mV
0.0013% from 0.12 V to 1000 V
.02 A.C. voltmeters
By the methods of - WI.WC.35
from 10 mV to 120 V
with least uncertainties of measurement of -
0.41% from 10 Hz to 20 kHz
0.62% from 20 kHz to 50 kHz
1.21% from 50 kHz to 100 kHz
from 120 V to 1000 V
with least uncertainties of measurement of -
0.26% from 50 kHz to 60 kHz
.03 D.C. ammeters
By the methods of - WI.WC.33; WI.WC.34
with least uncertainties of measurement of -
0.092% from 100 μA to 1 mA
0.25% from 1 mA to 10 mA
0.093% from 10 mA to 100 mA
0.22% from 100 mA to 1 A
0.19% from 1 to 10 A
0.092% from 10 to 400 A
.04 A.C. ammeters
By the methods of - WI.WC.37; WI.WC.38
with least uncertainties of measurement of -
0.51% from 10 Hz to 5 kHz from 10 mA to 1 A
0.47% from 50 Hz to 60 Hz and at 400 Hz from 1 to 20 A
0.41% from 50 Hz to 60 Hz from 20 to 100 A
.05 Wattmeters
DC power from 1 to 1000V and 0.1 to 400 A (limited to 50kW)
by the methods of - WI.WC.41
with least uncertainties of measurement of -0.62%
Active Power from 1 to 750 V and 0.1 to 100 A (limited to 50kW) at Unity Power-factor from 50 to 60 Hz
by the methods of - WI.WC.41
with least uncertainties of measurement of -
0.66%
3.07 Power supplies and stabilisers
DC Voltage from 1 mV to 1000 V by the methods of - WI.WT.31 with least uncertainties of measurement of -
0.57% from 1 mV to 10 mV
0.058% from 10 mV to 120 mV
0.013% from 0.12 V to 1000 V
A.C. voltage from 10 mV to 1000 V and 10 Hz to 100 kHz
by the methods of - WI.WT.35 from 10 mV to 120 V with least uncertainties of measurement of -
0.41% from 10 Hz to 20 kHz
0.62% from 20 kHz to 50 kHz
1.21% from 50 kHz to 100 kHz
from 120 V to 1000 V with least uncertainties of measurement of -
0.26% from 50 Hz to 60 Hz
D.C. current from 100 μA to 400 A
by the methods of - WI.WT.33; WI.WT.34 with least uncertainties of measurement of -
0.092% from 100 μA to 1 mA
0.25% from 1 mA to 10 mA
0.093% from 10 mA to 100 mA
0.22% from 100 mA to 1 A
0.19% from 1 to 10 A
0.092% from 10 to 400 A
A.C. current by the methods of - WI.WT.37; WI.WT.38 with least uncertainties of measurement of -
0.51% from 10 mA to 1 A from 10 Hz to 5 kHz
0.47% from 1 to 20 A from 50 Hz to 60 Hz and at 400 Hz
0.41% from 20 to 100 A from 50 Hz to 60 Hz
DC power by the methods of - WI.WT.41 from 1 to 1000 V and 0.1 to 400 A (limited to 50kW) with least uncertainties of measurement of -
0.62%
Active Power by the methods of - WI.WT.41
from 1 to 750 V and 0.1 to 100 A (limited to 50kW) at Unity Power-factor from 50 to 60 Hz
with least uncertainties of measurement of -
0.66%
.01 Power supplies
.03 Power conditioners
3.11 Power supply equipment and systems
.01 Electric parameters
DC Voltage from 1 mV to 1000 V by the methods of - WI.WT.31 with least uncertainties of measurement of -
0.57% from 1 mV to 10 mV
0.058% from 10 mV to 120 mV
0.013% from 0.12 V to 1000 V
A.C. voltage from 10 mV to 100 kHz and 10 Hz to 100 Hz by the methods of - WI.WT.35 from 10 mV to 120 V
with least uncertainties of measurement of -
0.41% from 10 Hz to 20 kHz
0.62% from 20 kHz to 50 kHz
1.21% from 50 kHz to 100 kHz
from 120 V to 1000 V with least uncertainties of measurement of -
0.26% from 50 Hz to 60 Hz
D.C. current from 100 μA to 400 A by the methods of - WI.WT.33; WI.WT.34
with least uncertainties of measurement of -
0.092% from 100 μA to 1 mA
0.25% from 1 mA to 10 mA
0.093% from 10 mA to 100 mA
0.22% from 100 mA to 1 A
0.19% from 1 to 10 A
0.092% from 10 to 400 A
A.C. current by the methods of - WI.WT.37; WI.WT.38 with least uncertainties of measurement of -
0.51% from 10 mA to 1 A from 10 Hz to 5 kHz
0.47% from 1 to 20 A from 50 Hz to 60 Hz and at 400 Hz
0.41% from 20 to 100 A from 50 Hz to 60 Hz
DC power by the methods of - WI.WT.41 from 1 to 1000 V and 0.1 to 400 A (limited to 50 kW)
with least uncertainties of measurement of -
0.62%
Active Power by the methods of - WI.WT.41 from 1 to 750 V and 0.1 to 100 A (limited to 50 kW) at Unity Power-factor from 50 to 60 Hz
with least uncertainties of measurement of -
0.66%
(Last Modified: 30-NOV-16 )